Fr Block Temperature Transmitter |
View
Large
|
The ABUS FrBlock Series is a head-mounted version of the Fixed Range Temperature Transmitter. FrBlock Series is used for RTD Pt-100 sensor input and Thermocouple input, converts a temperature sensor signal into a 4 to 20 mA DC current loop powered signal with excellent linearity and load driving capability.
The Transmitter is mounted on the head of the temperature sensor and accepts either a three-wire RTD Pt-100 sensor or a Thermocouple sensor and converts it into a linear current loop signal of 4 to 20 mA DC, capable of driving a load of up to 600 Ohms. The instrument operates in two-wire configuration. |
|
Sensor Input | : | Pt100, 3-wire connection, α = 0.00385, according to IEC 60751.
| Sensor Current | : | 0.3mA. | Sensor Break Detection | : | Upscale: ~ 25mA, Downscale: ~ 3mA. | Selection | : | Zero: -100°C ~ 70°C (-148°F ~ 158°F), Span: 25 ~ 650°C (42°F ~ 1202°F). | Adjustment | : | Zero: ± 10%, Span: ± 10%. | Current Limit | : | ~ 25mA. | Linearity & Calibration | : | Temperature Linear, ± 0.1% of span. | Permissible Load | : | 800Ω @ 24V DC, 22mA. | Power Supply | : | 6.5V DC ~ 32V DC. | Supply Voltage Effect | : | ± 0.002% of span / V. | Operating Temperature | : | -20 ~ 55°C (-5°F ~ 160°F). | Humidity | : | 0 to 95% RH. | Mounting | : | DIN B-head or larger. | Connection | : | ≤ 2.5mm², SWG 14. | Protection | : | IP20. | Weight | : | 70 g. | Material | : | Zinc Alloy. | Dimensions | : | 44mm (Diameter) x 21mm (Height). |
|
|
[FRBlock_Temperature_Transmitter.pdf]
|
|
|
|
|